No.
Register
No. for
Trans-
mission
Name
Initial
Setting
User
Setting
Ref.
Page
44
012CH
Monitor item selection
0: Output frequency
1: Output current
0
78
45
012DH
Monitor gain
Setting unit: 0.01
Setting range: 0.01 ~ 2.00
1.00
78
46
012EH
Carrier frequency
Set value: 1 ~ 4 carrier frequency = set
value ¥ 2.5kHz
Set value: Synchronous type of 7 ~ 9
lower limit 1kHz and upper limit 2.5 kHz
4(Note 3)
79
47
012FH
Operation selection after
momentary power loss
0: Operation does not continue.
1: Operation continues within momen-
tary power ride through time
2: Operation always continues. (No
UV1 fault detection)
0
70
48
0130H
Fault reset
Setting unit: time
Setting range: 0 ~ 10 times
0 time
75
49
0131H
Jump frequency 1
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.00 ~ 400Hz
(Note) If 0.0Hz is set, jump frequency 1
is enabled.
0.0Hz
75
50
0132H
Jump frequency 2
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.00 ~ 400Hz
(Note) If 0.0Hz is set, jump frequency 2
is disabled.
0.0Hz
75
51
0133H
Jump frequency width
Setting unit: 0.1Hz
Setting range: 0.0 ~ 25.5Hz
(Note) If 0.0Hz is set, jump frequencies
1 ~ 2 are disabled.
0.0Hz
75
52
0134H
DC injection braking
current
Setting unit: 1%
Setting range: 0 ~ 100%
(note) If 0% is set, it becomes base-
block status.
50%
76
53
0135H
DC injection braking time
at stop
Setting unit: 0.1s
Setting range: 0.0 ~ 25.5s
(Note) If 0.0s is set, this function will no
operate.
0.0s
83
54
0136H
DC injection braking time
at start
Setting unit: 0.1s
Setting range: 0.0 ~ 25.5s
(Note) If 0.0s is set, this function will not
operate.
0.0s
76
55
0137H
Stall prevention (current
limit) during decel
0: Stall prevention function is enabled
during deceleration.
1: Stall prevention function is disabled
during deceleration.
0
92
56
0138H
Stall prevention (current
limit) during accel
Setting unit: 1%
Setting range: 30 ~ 200%
(Note): If set at 200%, this function will
not operate.
(Note): For rated output range, the
operator level is automatically reduced.
170%
91