108

Protective
Operation

Output is shut
OFF and motor
coasts to a
stop.

OH (Cooling fin overheat)
Temperature rise because of
inverter overload operation or
intake air temperature rise.

• Excessive load
• Improper V/f pattern

setting

• Insufficient axel time

if the fault occurs
during acceleration.

• Intake air

temperature
exceeding 122

°

F

(50

°

C)

• Calling fan stops

Check the following:
• Load size
• V/f pattern setting

(parameters n11 to
n17)

• Intake air

temperature

OL1 (Motor overload)
Motor overload protection
operates by built-in electronic
thermal overload relay.

• Check the load size

or V/f pattern setting
(parameters n09 to
n15)

• Set the motor rated

current shown on the
nameplate by
parameter n36.

OL2 (Inverter overload)
Inverter overload protection
operates by built-in electronic
thermal overload relay.

• Check the load size

or V/f pattern setting
(parameters n09 to
n15)

• Check the inverter

capacity.

OL3 (Over torque detection)
Inverter output current

exceeded the preset value in
parameter n60.

When over torque is detected,
inverter performs operation
according to the preset setting
of parameter n59.

Check the driven
machine and correct
the cause of the fault,
or increase the value of
parameter n60 up to
the highest value
allowed for the
machine.

Alarm Display

Inverter

Status

Explanation

Causes and

Corrective Actions

Digital

Operator

RUN ALARM

(Green) (Red)