Yaskawa VS mini J7 Series User Manual
Page 105

105
Blinking
Warning
Fault contacts
do not change
state.
OP! (parameters setting
error when the parameters
setting is performed through
the MEMOBUS
communications)
OP1: Two or more values are
set for multi-function
input selection.
(parameters n36 to
n39)
OP2: Relationship among
V / f parameters is not
correct.
(parameters n09, n11,
n12, n14)
OP3: Setting value of motor
rated current exceeds
120% of inverter rated
current. (parameter
n32)
OP4: Upper/lower limit of
frequency reference is
reversed. (parameters
n30, n31)
OP5: Setting values of jump
frequencies 1 and 2 are
not appropriate.
(parameters n49 to
n50)
OP9: Carrier frequency
setting is incorrect.
(parameter n46)
Check the setting
values.
Blinking
OL 3 (Over torque detection)
Motor current exceeded the
preset value in parameter
n98.
Reduce the load and
expand the accel/decel
time.
Blinking
SER (Sequence error)
Inverter receives LOCAL/
REMOTE select command or
communication/control circuit
terminal changing signals
from the multi-function
terminal while the inverter is
outputting.
Check the external
circuit (sequence).
Alarm Display
Inverter
Status
Explanation
Causes and
Corrective Actions
Digital
Operator
RUN ALARM
(Green) (Red)