78

Determines whether output frequency or output current is indicated on the analog
output terminals, AM-AC, for monitoring.

Initial setting-analog voltage of approx. 10V is output when output frequency (output
current) is 100%.

Used to adjust analog output gain.

Scales the analog output voltage signal level at 100% of output frequency (output
current).

Example: Frequency meter displays 0 to 60Hz with 0 to 3V.

10V x n45 setting (0.30V) = 3V (3V is output at 100% output frequency)

Using a frequency meter or ammeter (n44)

Setting

Description

0

Output frequency

1

Output current

Calibrating frequency meter or ammeter (n045)