Motor Overload Protection
Electronic thermal overload relay
Instantaneous Over Current
Motor coasts to a stop at approx. 200% of inverter
rated current
Overload
Motor coasts to a stop after 1 minute at 150% of
inverter rated output current
Over Voltage
Motor coasts to a stop if DC bus voltage exceed
820V
Under Voltage
Stops when DC bus voltage is approx. 400V or less
Momentary Power Loss
Following items are selectable: Not provided (stops if
power loss is 15ms or longer), continuous operation
if power loss is approx. 0.5s or shorter, continuous
operation
Cooling Fin Overheat
Protected by electronic circuit
Stall Prevention Level
Individual levels during accel/running, enable/disable
provided during deceleration.
Cooling Fan Fault
Protected by electronic circuit (fan stalling detection)
Ground Fault
Protected by electronic circuit (rated output current
level)
Ot
he
r
F
u
n
c
ti
o
n
s
Power Charge Indication
Charge LED is provided
On until the DC bus voltage becomes 50V or less.
Inpu
t S
ig
nal
s
Multi-function Input
Four of the following input signals are selectable:
Reverse run (3-wire sequence), fault reset, external
fault (NO/NC contact input), multi-step speed
operation, Jog command, accel/decel time select,
external baseblock (NO/NC contact input), speed
search command, accel/decel hold command,
LOCAL/REMOTE selection, communication/control
circuit terminal selection, emergency stop fault,
emergency stop alarm
Ou
tp
ut
S
ig
na
ls
Multi-function Output
Following output signals are selectable (1 NO/NC
contact output,):
Fault, running, zero speed, at frequency, frequency
detection (output frequency
≤
or
≥
set value), during
over torque detection, during under voltage
detection, minor error, during baseblock, operation
mode, inverter run ready, during fault retry, during
UV, during speed search, data output through
communication
Standard Functions
Full-range automatic torque boost, slip
compensation, DC injection braking current/time at
start/stop frequency reference bias/gain, frequency
reference with built-in volume, [MEMOBUS
communications (RS-485/422, max. 19.2K).]
Voltage Class
400V 3-phase
Model
CIMR-J7A!!!!
3-phase
40P2
40P4
40P7
41P5
42P2
43P7