Connection phases

1

Overvoltage category as per IEC 60664-1

III

Protective Devices

Overvoltage protection

Varistors

Maximum permissible fuse protection

16 A

General Data

Width x height x depth, without connection area

162 mm x 90 mm x 68 mm

Weight

0.75 kg

Climatic category in accordance with IEC
60721-3-4

4K1

Environmental category

Not air-conditioned, indoors

Pollution degree outside the enclosure

3

Pollution degree inside the enclosure

2

Operating temperature range

−40°C to +45°C

Maximum permissible value for relative humid-
ity, non-condensing

100%

Maximum operating altitude above mean sea
level

3,000 m

Cooling method

Convection

Degree of protection for electronics in accor-
dance with IEC 60529

IP20

Protection class in accordance with IEC 61140

I

Grid configurations

TN-C grid configuration, TN-S grid

configuration, TN-C-S grid configuration, Delta-IT

*

Approvals and national standards
As of June 2014

VDE0126-1-1, VDE-AR-N-4105, VFR2014, PPC,

EN 50438-CZ, NEN-EN 50438, EN 50438,

C10/11/2012, AS 4777.3, RD1699, G83/2,

CEI0-21, IEC 62109-2**

* Delta-IT: When using in these networks, the grounding conductor monitoring must be deactivated and

an additional grounding connected to the inverter.

** IEC 62109-2: This standard requires that the PV system is connected to Sunny Portal and that the fault

alert is activated in Sunny Portal.

14 Technical Data

SMA Solar Technology AG

Installation Manual

SMA-SB240-IA-en-12

70