Event
number
Event, cause and corrective measures
1001
Installation failure grid connection / L/N swapped (1001)
The conductors L and N are swapped or PE is not connected.
Corrective measures:
• Check whether the connecting terminal plates Grid and Inverter of the
Sunny Multigate are correctly assigned.
• If the connecting terminal plates Grid and Inverter are not correctly assigned,
disconnect the Sunny Multigate from all voltage sources (see Section 10, page
50) and connect the conductors L, N and PE correctly.
• Once the connecting terminal plates are correctly assigned, check whether the
AC field plugs or junction boxes between the inverters and the Sunny Multigate
are correctly assembled.
– Disconnect the inverter from all voltage sources (see Section 9, page 48).
– Check the assembling. If present, remove the AC field plug (see
Section 13.1 "Disconnecting the AC Field Plug", page 64) and assemble it
correctly (see Section 6.4 "Assembling the AC Field Plug", page 33).
• If the connecting terminal plates Grid and Inverter of the Sunny Multigate are
correctly assigned, the inverter is correctly connected, the AC field plugs or
junction boxes used are correctly assembled and this message is still displayed,
contact the SMA Service Line.
6002
Self diagnosis > Interference of device (6002)
The system data is defective.
Corrective measures:
• Download firmware update from www.SMA-Solar.com and install with Sunny
Explorer.
• If this message is still displayed, contact the SMA Service Line.
6415
Self diagnosis > Interference of device (6415)
The reference voltage test failed.
Corrective measures:
• Disconnect the Sunny Multigate from voltage sources (see Section 10, page 50)
and re-commission it (see Section 7, page 42).
• If this message is still displayed, contact the SMA Service Line.
6702
Interference device (6702)
The cause must be determined by the SMA Service Line.
Corrective measures:
• Contact the SMA Service Line.