Event
number
Event, cause and corrective measures
7001
Fault sensor interior temperature (7001)
The temperature sensor for the indoor temperature of the Sunny Multigate is defective.
Feed-in operation will be interrupted.
Corrective measures:
• Contact the SMA Service Line.
7702
Self diagnosis > Interference of device (7702)
A relay error has occurred.
Corrective measures:
• Disconnect the Sunny Multigate from voltage sources (see Section 10, page 50)
and re-commission it (see Section 7, page 42).
• If this message is still displayed, contact the SMA Service Line.
8101 to
8102
Communication disturbed (8101, 8102)
An error has occurred in the internal communication. This can be caused by one of the
following: Feed-in operation continues.
Corrective measures:
1. If several Sunny Multigate devices are installed in a system, check whether the
AC cables from the inverters to the Sunny Multigate devices have been laid in
separate channels. If the AC cables are not laid separately from each other, lay
the AC cables from the inverter to the Sunny Multigate in separate locations.
2. If the problem persists, contact the SMA Service Line.
8104
Interference device (8104)
The cause must be determined by the SMA Service Line.
Corrective measures:
• Contact the SMA Service Line.
9014
Invalid device combination (9014)
The Sunny Multigate and the inverters cannot be operated in this combination.
Corrective measures:
1. Contact the SMA Service Line and request the latest firmware update, if
necessary.
9015
Max. permitted number of inverters exceeded (9015)
The number of inverters connected exceeds the maximum number specified in the cur-
rently set standard.
Corrective measures:
• Reduce the number of inverters in the PV system until the maximum permissible
number is reached (see the user manual of the communication product).