14 technical data, 1 requirements for the pv modules, 2 sunny boy 240 – SMA SB 240 User Manual
Page 66

14 Technical Data
14.1 Requirements for the PV Modules
Maximum DC power at standard test condition-
s (STC)
300 W
MPP voltage range at standard test condition-
s (STC)
26 V to 32 V
Maximum short-circuit current at standard test
conditions (STC)
12 A
14.2 Sunny Boy 240
DC Input
Maximum number of connected PV modules per
inverter
1
Maximum input voltage
45 V
MPP voltage range at 230 V
23.0 V to 39.0 V
Rated input voltage
29.5 V
Minimum input voltage
23.0 V
Minimum initial input voltage
23.0 V
Maximum initial input voltage
40 V
Maximum input current
8.5 A
Maximum short-circuit current per module*
12 A
Overvoltage category as per IEC 60664-1
II
* In accordance with IEC 62109-2: ISC PV
AC Output
Rated power at 230 V, 50 Hz
230 W
Maximum apparent AC power
230 VA
Rated grid voltage
230 V
Nominal AC voltage
220 V / 230 V / 240 V
AC voltage range
184 V to 270 V
Nominal AC current at 220 V
1 A
Nominal AC current at 230 V
1 A
Nominal AC current at 240 V
0.96 A
14 Technical Data
SMA Solar Technology AG
Installation Manual
SMA-SB240-IA-en-12
66