2 sunny multigate, 3 ac cabling of the inverters, Sunny multigate – SMA SB 240 User Manual

Page 31: Ac cabling of the inverters

background image

6.2.2

Sunny Multigate

Figure 15: Connection areas on the Sunny Multigate

Position

Designation

A

Connecting terminal plate for the connection of the AC cable of the in-
verter, labeling: Inverter

B

Pin connector for connecting the optional communication

C

Pin connector for connecting the network cable (RJ45)

D

Connecting terminal plate for the connection of the AC cable of the utility
grid, labeling: Grid

6.3 AC Cabling of the Inverters

Figure 16: AC cabling among the inverters (left = last inverter; right = first inverter)

Requirements:

☐ For fusing purposes, use at maximum a 16 A circuit breaker.
☐ No loads must be connected between the individual inverters.

6 Electrical Connection

SMA Solar Technology AG

Installation Manual

31

SMA-SB240-IA-en-12