3 sunny multigate – SMA SB 240 User Manual
Page 69

AC connection
AC cable with two connectors**
Powerline interface
As standard
* The DC connectors supplied are dependent on the order. You can find the SMA order numbers of the
DC connectors in this document (see Section 15 "Spare Parts and Accessories", page 72).
** The length of the AC cable depends on the order and is either 1.40 m or 2.0 m.
Efficiency
Maximum efficiency, η
max
95.8%
European efficiency, η
EU
95.3%
14.3 Sunny Multigate
AC Input
Maximum number of connected micro inverters
12
Minimum number of connected micro inverters
1
Maximum input current
12 A
AC Output
Rated power at 230 V, 50 Hz
2,760 W
Rated grid voltage
230 V
Nominal AC voltage
220 V / 230 V / 240 V
AC voltage range
184 V to 270 V
Nominal AC current at 220 V
12 A
Nominal AC current at 230 V
12 A
Nominal AC current at 240 V
11.5 A
Maximum output current
12 A
Total harmonic distortion of the output current
with total harmonic distortion of the AC voltage
< 2%, and AC power > 50% of the rated power
≤ 3%
Rated power frequency
50 Hz
AC power frequency
50 Hz / 60 Hz
Operating range at AC power frequency 50 Hz
45.5 Hz to 63 Hz
Operating range at AC power frequency 60 Hz
45.5 Hz to 63 Hz
Power factor at rated power
1
Feed-in phases
1
14 Technical Data
SMA Solar Technology AG
Installation Manual
69