11 Troubleshooting
11.1 Error Messages
During operation of the PV system, events may occur which can refer to one or several inverters or
the Sunny Multigate. Events can be information, warnings or errors. All events are displayed in the
communication product you are using (e.g. Sunny Portal, Sunny Explorer). Sunny Explorer
additionally displays the corresponding event number for each event.
Inverter
Event
number
Event, cause and corrective measures
101
Grid fault/Grid overvoltage (spot value) (101)
The grid voltage or grid impedance at the connection point is too high. The inverter
has disconnected from the utility grid.
Corrective measures:
• Check whether the grid voltage at the connection point is permanently in the
permissible range.
If the grid voltage is outside the permissible range due to local grid conditions,
contact the grid operator. The grid operator must approve changes to the
operating parameters of the inverter.
If the grid voltage is permanently within the permissible range and this message is
still displayed, contact the SMA Service Line.
102
Grid fault / Grid overvoltage fast (102)
The grid voltage or grid impedance at the connection point of the inverter is too high.
The inverter has disconnected from the utility grid.
Corrective measures:
• Check whether the grid voltage at the connection point of the inverter is
permanently in the permissible range.
If the grid voltage is outside the permissible range due to local grid conditions,
contact the grid operator. The grid operator must approve changes to the
operating parameters of the inverter.
If the grid voltage is permanently within the permissible range and this message is
still displayed, contact the SMA Service Line.