Technical specifications, Table c.1, Echnical – RLE Protocol Converter V.2.4 User Manual
Page 69: Pecifications
rletech.com
Protocol Converter User Guide
69
A
P P E N D I X
C
HAPTER
0
T
ECHNICAL
S
PECIFICATIONS
Table C.1 Technical Specifications
Power
24VAC @ 600mA max, 50/60Hz, 24VDC @ 600mA max.
Communications Ports
Ethernet
10/100 BASE-T, RJ45 connector; 500VAC RMS isolation
EIA-232
DB9 female connector; 9600 baud; No parity, 8 data bits,
1 stop bit
EIA-485 (Dual Port Protocol
Converter contains 3 EIA-485 ports)
1200, 2400, 9600 or 19200 baud (selectable); Parity: none,
even or odd, 8 data bits, 1 stop bit. Port 2 is configurable for
half-duplex (2-wire) or full-duplex (4-wire)
Protocols
TCP/IP, HTML, TFTP, SNMP
V1: V2C MIB-2 compliant; NMS Manageable with Get
Modbus (EIA-485)
Modbus Master/Slave; RTU mode; Supports Master codes
01, 02, 03, 04 and Slave code 03
Modus TCP/IP UDP/IP
Modbus Master/Slave; TCP/IP transmission protocol
BACnet/IP
ASHRAE STD 135-2004 Annex J; Port 3 of Dual Port
Protocol Converter is BACnet MS/TP capable (Slave only)
SMTP (email)
Supports Client Authentication (plain and login); compatible
with ESMTP servers
Terminal Emulation
VT100 compatible (for configuration and diagnostics only)
Protocols In
SNMP, Modbus TCP/IP & RTU, BACnet
Protocols Out
SNMP, Modbus TCP/IP & RTU, BACnet; BACnet MS/TP
(Port 3 of Dual Port Protocol Converter only)
Login Security
Web Browser Access (Ethernet)
1 Web password Read Only; 1 Web password Read/Write
Terminal Emulation Access
None
Maximum Number of Units/Modules/Nodes
32