4.3. RTU

Framing

The example below shows a typical Query/Response from an Protocol Converter Wireless

System.

Slave address 2 responds to Function Code 4 with six bytes of hexadecimal data and ends with

CRC16 checksum.

Register Values:

40001 = 0000 (hex)

40002 = 0000 (hex)

40003 = 0001 (hex)

Table 4.2 Read Output Registers Packet Structure

Read Registers Request Packet

Read Registers Response Packet

Slave Address (1 byte)

Slave Address (1 byte)

03 (Function code) (1 byte)

03 (Function code) (1 byte)

Start Register (2 bytes)

Byte count (1 byte)

# of registers to read (2 bytes)

First register (2 bytes)

CRC Checksum (2 bytes)

Second register (2 bytes)

CRC Checksum (2 bytes)

Table 4.3 Output Registers

Register

Name

Description

Units

Range

40001

Integer Output

Register for Integer data

uint16

0-65535

42001

Float Output
* two registers need

Register for Float data

Uint32

0-65535

Table 4.4 Response Sample

Slave

Address

Function

Code

Count Bytes

of Data

Register

Data

Msb Lsb

Register

Data

Msb Lsb

Register

Data

Msb Lsb

CRC 16

“Lsb”

CRC 16

“Msb”

02

04

06

00 00 00 00 00 01 B5

A3