Figure 3.28 bacnet pics information – RLE Protocol Converter V.2.4 User Manual
Page 49

rletech.com
Protocol Converter User Guide
49
3
Configuration
Figure 3.28
BACnet PICS Information
UDP Port
This is the user datagram protocol port, which is used by
applications to send messages to a device (in this case, the
Protocol Converter).
Enter 0 to specify port 47808 as the UDP port. If another
port is specified by your application, enter a new port
number in this field.
Default setting: 0 (47808)
BACnet-MS/TP Port3 Max
Master
Set the slave address, 1/127. 0 = slave only.
Default setting: 0
BACnet/IP Read-Multiple
Enable or disable this feature.
BACnet PICS link
This link displays the protocol implementation conformance
statement (PICS). The PICS Web page shows general
BACnet capabilities of the device (for example, available
LAN options). An example of a BACnet PICS page is
shown in
.
Engineering Units
Click this link to view a list of the units supported by the
device, coupled with their numerical BACnet identifiers.
BACnet/IP COV Clients
This is a list of the BACnet clients that will receive a
notification when the Protocol Converter notes a change of
value (COV).
Configure these addresses on the Registers tab.
BACnet BBMD-BDT
This feature is used by some BACnet masters for discovery
on different subnets. Enter information as applicable to
your application.
Option
Description
Table 3.9
BACnet Server Configuration Options (continued)