Set communication protocol options, 1 modbus/eia-485 port configuration, Modbus/eia-485 port configuration – RLE Protocol Converter V.2.4 User Manual
Page 46: Table 3.8

46
Protocol Converter User Guide
800.518.1519
3
Configuration
3.7.
Set Communication Protocol Options
Set the Modbus, BACnet, or SNMP protocols as described in the following sections.
3.7.1 Modbus/EIA-485 Port Configuration
To configure the Modbus/EIA-485 port, use the top navigation bar to access the Configuration
screens. Select the EIA-485/Modbus/BACnet-MSTP Ports option and configure the fields
accordingly.
Figure 3.26
EIA-485/Modbus/BACnet-MSTP Ports Configuration
Option
Description
Modbus/TCP/UDP Slave
Unit Identifier
Designate the TCP/UDP slave address in the range 1 to 254.
To disable this feature, leave the address set to 0.
Offline Startup Delay
Amount of time, in minutes, that the Protocol Converter waits
before considering any slave device as offline after a power up.
Table 3.8
EIA-485/Modbus/BACnet-MSTP Ports Configuration Options