3 modbus register configuration, Modbus register configuration, Figure 3.13 modbus register configuration – RLE Protocol Converter V.2.4 User Manual
Page 35: Table 3.5
![background image](https://www.manualsdir.com/files/802982/content/doc035.png)
rletech.com
Protocol Converter User Guide
35
3
Configuration
3.6.3 Modbus Register Configuration
If you are configuring a Modbus device, the register configuration page looks like this:
Figure 3.13
Modbus Register Configuration
1
Type an appropriate value in each field, or choose the value from the drop-down.
Option
Description
Unit
This is the unit number of the register you’re configuring.
Modbus Register
The Modbus register to be polled by the Protocol Converter
to that specific slave. The Protocol Converter can poll Coil
registers (1x,) Status registers (2x), Input registers (3x),
and Holding registers (4x). Type a value in the range of
0000 to 49999 or 410000 to 465535.
Register Type
The register type. Choose Unsigned Integer, Signed
integer, Long, Float, Alarm Bit / ON=ALARM, Alarm Bit /
OFF=ALARM, Status Bit, Coil Status, Input Status, or
Int64.
Table 3.5
Modbus Register Configuration Page Options