Configure device registers, 1 enable write operations to devices, Enable write operations to devices – RLE Protocol Converter V.2.4 User Manual
Page 33

rletech.com
Protocol Converter User Guide
33
3
Configuration
3.6.
Configure Device Registers
Once the desired slave devices have been configured on the Protocol Converter, you can
program registers to those slave devices for the proper information to be polled. First, you can
select whether or not to enable write operations to the slave devices, then you can program the
registers.
NOTE
You can also delete the Protocol Converter’s entire register set. Make sure to consider this
operation carefully before carrying it out.
3.6.1 Enable Write Operations to Devices
To enable the ability to write values to Modbus, SNMP, and BACnet device registers:
1
Click the Configuration link in the menu bar. From the Configuration menu, click the
EIA-485/Modbus/BACnet-MSTP Ports link.
2
In the top section of the EIA-485/Modbus/BACnet-MSTP Ports page, select Yes to enable
the Device Write option:
The write operations are generated via Modbus preset single-register commands, SNMP
sets, and BACnet write-property operations. Refer to the following sections on configuring
Modbus, SNMP, and BACnet registers for more information about generating write
operations through the Protocol Converter’s user interface.