Technical specifications, Table e.1, Echnical – RLE LD5100 User Manual
Page 71: Pecifications
www.rletech.com
71
970.484.6510
A
P P E N D I X
C
HAPTER
0
T
ECHNICAL
S
PECIFICATIONS
Table E.1 Technical Specifications
Power
100-240VAC @ 500mA Max, 50/60 Hz; hardwired power
supply
Inputs
Water Leak Detection Cable
Compatible with SeaHawk SC Cable (not included)
Cable Input
Requires SeaHawk LC-KIT: 15ft (4.57m) leader cable and
EOL (LC-KIT not included)
Maximum Length
5,000ft (1,524m)
Detection Accuracy
± 2ft (0.6m)+/- 0.5% of the cable length
Detection Repeatability
± 2ft (0.6m) +/- 0.25% of the cable length
Detection Response Time
5-990sec, software adjustable in 5sec increments; ±2sec
Outputs
Analog
4-20mA Loop Powered, 18-36VDC, RL = 500? max.
Relay
2 Form C Leak Relays, 2 Form C Cable Break Relays; 1A
@ 24VDC, 0.5A resistive @ 120VAC; configurable for
supervised or non-supervised, latched or non-latched
Communications Ports
RS-232
9600 baud; No parity, 8 data bits, 1 stop bit
RS-485
1200, 2400, 9600 or 19200 baud (selectable);
No parity, 8 data bits, 1 stop bit
Protocols
Modbus (RS-485)
Slave; RTU Mode; Supports function codes 03, 04, 06 and
16
Terminal Emulation (RS-232)
VT100 compatible
Alarm Notification
Audible Alarm
85DBA @ 2ft (0.6m); re-sound 0-999min