Installation

Figure 3.3 Lower Right Terminal Block

Once the three wires are connected inside the terminal block, turn the AC power supply back

on. The LD5100 should begin booting up. Wait approximately one minute. No alarm should

be present.

On the LCD, press any key for the main menu. Enter the Cable Status menu. The cable length

is displayed. If this reading varies by more than ±5% of the actual length of cable installed,

verify the installation.

Through the LCD submenus, you may set the clock, system name, alarm configuration, feet/

meters, etc.

Wait at least 30 minutes before calibrating the LD5100. Calibrate the LD5100 through the

front panel System Setup menu.

Map the cable per the instructions in Chapter 6, “Mapping the Cable” on page 41.