Table 8.5, Input registers – RLE LD5100 User Manual
Page 54
www.rletech.com
54
970.484.6510
8
Modbus Communication
Table 8.5 Input Registers
Register
Name
Description
Units
Range
30001
Status
Bit level status
None
0-65535
30002
Leak Distance
Location of leak
Ft/Meters
0-65535
30003
Units
Unit of measure
1=Ft
0=Meters
0-65535
30004
Leak Current
Leakage current on cable
Amps
0-65535
30005
Cable Length
Installed cable length
Ft/Meters
0-65535
30006
Loop1 Res
Resistance of cable
Ohms
0-65535
30007
Loop2 Res
Resistance of cable
Ohms
0-65535
30008
Res/Ft
Resistance of cable Ohms
x1000
0-65535
30009
Version
Firmware version
xx.xx X 100
0-65535
30010
Virtual Zone Alarm Status
Bit Level Status
None
0-65535
30011
Modbus Zone Enabled Flags
Bit Level Status
None
0-65535
30012
Modbus Zone2 Status
Bit Level Status
None
0-65535
30013
Modbus Zone2 Distance
Location of leak
Ft/Meters
0-65535
30014
Modbus Zone3 Status
Bit Level Status
None
0-65535
30015
Modbus Zone3 Distance
Location of leak
Ft/Meters
0-65535
30016
Modbus Zone4 Status
Bit Level Status
None
0-65535
30017
Modbus Zone4 Distance
Location of leak
Ft/Meters
0-65535
30018
Modbus Zone5 Status
Bit Level Status
None
0-65535
30019
Modbus Zone5 Distance
Location of leak
Ft/Meters
0-65535
30020
Modbus Zone6 Status
Bit Level Status
None
0-65535
30021
Modbus Zone6 Distance
Location of leak
Ft/Meters
0-65535
30022
Modbus Zone7 Status
Bit Level Status
None
0-65535
30023
Modbus Zone7 Distance
Location of leak
Ft/Meters
0-65535
30024
Modbus Zone8 Status
Bit Level Status
None
0-65535
30025
Modbus Zone8 Distance
Location of leak
Ft/Meters
0-65535
30026
Modbus Zone9 Status
Bit Level Status
None
0-65535
30027
Modbus Zone9 Distance
Location of leak
Ft/Meters
0-65535
30028
Modbus Zone10 Status
Bit Level Status
None
0-65535
30029
Modbus Zone10 Distance
Location of leak
Ft/Meters
0-65535
30030
Modbus Zone11 Status
Bit Level Status
None
0-65535
30031
Modbus Zone11 Distance
Location of leak
Ft/Meters
0-65535
30032
Modbus Zone12 Status
Location of leak
None
0-65535
30033
Modbus Zone12 Distance
Bit Level Status
Ft/Meters
0-65535
Registers 30011 through 30033 are dedicated registers for modbus master; see Appendix B, “Leak