Table 8.3, Output registers – RLE LD5100 User Manual

Page 52

background image

www.rletech.com

52

970.484.6510

8

Modbus Communication

Table 8.3 Output Registers

Register

Name

Description

Units

Range

40001

Leak Threshold

Trip current for leak alarm

Amps

0-65535

40002

Contamination

Threshold

Trip current for contamination alarm

Amps

0-65535

40003

Re-Alarm

Re-Alarm delay

Minutes

0-65535

40004

Latched Alarm

Latching Alarms 0=No

1=Yes

0-65535

40005

Silence Alarm

Set to 1 to silence audible alarm

1=Silence

0-65535

40006

Reset Alarm

Set to 1 to reset alarms

1=Reset

Alarm

0-65535

40007

Spare

0-65535

40008

Spare

0-65535

40009

Spare

0-65535

40010

Month

Clock

1-12

0-65535

40011

Day

Clock

1-31

0-65535

40012

Year

Clock

00-99

0-65535

40013

Hour

Clock

0-23

0-65535

40014

Minutes

Clock

0-59

0-65535

40015

Seconds

Clock

0-59

0-65535

40016

Seconds

Leak Alarm Delay

20-3600

0-65535

40017

Seconds

Contamination Alarm Delay

20-3600

0-65535