Table 8.6, Status flags (register 30001), Table 8.7 – RLE LD5100 User Manual
Page 55: Status flags (register 30010)
www.rletech.com
55
970.484.6510
8
Modbus Communication
Table 8.6 Status Flags (Register 30001)
Bit
Description
00
1 = Leak is Detected
01
1 = Cable Break Alarm
02
1 = Contamination is detected
03-15
Spare
Table 8.7 Status Flags (Register 30010)
Bit
Description
00
1 = Zone1
01
1 = Zone2
02
1 = Zone3
03
1 = Zone4
04
1 = Zone5
05
1 = Zone6
06
1 = Zone7
07
1 = Zone8
08
1 = Zone9
09
1 = Zone10
10
1 = Zone11
11
1 = Zone12
See also other documents in the category RLE Equipment:
- LD2000 Quick Start (2 pages)
- LD300 (2 pages)
- LDZ4 (19 pages)
- LD2000 (78 pages)
- LD5100 Quick Start (2 pages)
- LD310 (2 pages)
- LD5000 Quick Start (4 pages)
- LD1000 (2 pages)
- 10K Quick Start (2 pages)
- F200 (2 pages)
- LDRA6 Quick Start (2 pages)
- 10K V.2.5.a (44 pages)
- LD1500 Quick Start (2 pages)
- LD5000 (92 pages)
- LD2100 Quick Start (2 pages)
- LD5200 Quick Start (2 pages)
- LD1500 V.3.1 (52 pages)
- FDS-Wi Quick Start (2 pages)
- GD100 (26 pages)
- FDS-Wi V.2.5 (74 pages)
- LD2100 V.2.6 (92 pages)
- LD5200 V.2.3 (118 pages)
- F-Series Quick Start (2 pages)
- F110 Quick Start (2 pages)
- Wi-MGR Quick Start (2 pages)
- Wi-MGR V.1.6 (74 pages)
- FMS Quick Start (2 pages)
- FMS32 (92 pages)
- Ground Fault Monitor (2 pages)
- RA1x2 (2 pages)
- Protocol Converter Quick Start (2 pages)
- Protocol Converter V.2.4 (70 pages)
- Falcon EM (146 pages)
- FMS V.1.13 (226 pages)