Installation, Installing the unit, Nstallation – RLE LD5100 User Manual
Page 25
www.rletech.com
25
970.484.6510
C
H A P T E R
C
HAPTER
0
I
NSTALLATION
3.1.
Installing the Unit
The LD5100 is a wall mounted device. To secure the device to the wall, first remove the
aluminum back panel and all electronics from the enclosure. There are knockouts on the top
and bottom of the enclosure designed to accommodate. 5 inch (12.7mm) conduit. Remove as
many as necessary. There are two holes in the top back of the unit spaced 11 inches (.28m)
apart. Use drywall anchors or suitable anchors depending on the wall construction, to secure
the unit to the wall. Put two more anchors through the two holes in the bottom back of the unit.
Reinstall the back panel and reconnect the electronics.
3.2.
Connecting the SeaHawk Water Leak Detection
Cable (SC)
The LD5100 requires a leader cable kit (part #LC-KIT; purchased separately) which includes
a 15 foot (4.57m) leader cable. One end of this leader cable connects into the LD5100. This
end of the cable has four stripped, bare wires. The other end features a mating connector which
connects with the Sea Hawk Leak Detection Cable (SC). The end of the cable is finished with
a removable end terminator (EOL).
Note A Leader Cable Kit (part #LC-KIT) is required to connect the LD5100 to the SeaHawk Leak
Detection Cable (SC). The kits are not included with the LD5100 and can be purchased
separately.
Connect the 15 foot (4.57m) leader cable to the LD5100. From left to right, with the screws of
the terminal block connector facing up, the wires that screw into the terminal connector should
be colored white, black, green, and red. If the terminal connector is removed from the end of
the cable, make sure the wires are in this same order when the connector is reapplied.