Other main menu functions, Table 7.2 – RLE LD5100 User Manual
Page 47
www.rletech.com
47
970.484.6510
7
EIA-232 Interface
7.4.
Other Main Menu Functions
The remainder of the functions available from the Main Menu of the EIA-232 interface are
described in Table 7.2.
Table 7.2 Other Main Menu Functions
Option
Description
LS – Leak Status
LS displays the current cable readings, including both
cable length and any present current leakage.
AR – Alarm Reset
AR resets all alarm relays. This command forces all alarms
off. If an alarm condition is still present after the AR
command is executed, the alarm is reactivated. If an alarm
is still active after the AR command is executed, it will not
be re-entered in the Alarm History Log.
AH – Alarm History
AH displays the Alarm History Log.
CH – Clear Alarm History
CH clears the Alarm History Log.
TD – Trend Data Table
TD displays the Trend Data Table, which monitors and
displays leakage current.
CT – Clear Trend Data Table
CT clears all records from the Trend Data Table.
TI – Display Date/time
TI displays the LD5100’s current date and time
MT ON – Measurement Trace
On
MT ON displays advanced manufacturer diagnostics of the
microprocessor.
MT OFF – Measurement
Trace Off
MT OFF turns off the display of advanced manufacturer
diagnostics of the microprocessor.
MBT – Modbus Trace On
MBT shows Modbus trace.
MBS – Modbus Stats
MBS shows Modbus stats.
EX – Exit
EX is used to enter the Bootloader command section. The
unit will stop monitoring cable and allow firmware updates
to be loaded. To restore normal operation after updating
firmware, type RUN and press the Enter (<-|) key on the
keyboard, or power the unit off and then back on again.