EIA-232 Interface

7.4.

Other Main Menu Functions

The remainder of the functions available from the Main Menu of the EIA-232 interface are

described in Table 7.2.

Table 7.2 Other Main Menu Functions

Option

Description

LS – Leak Status

LS displays the current cable readings, including both

cable length and any present current leakage.

AR – Alarm Reset

AR resets all alarm relays. This command forces all alarms

off. If an alarm condition is still present after the AR

command is executed, the alarm is reactivated. If an alarm

is still active after the AR command is executed, it will not

be re-entered in the Alarm History Log.

AH – Alarm History

AH displays the Alarm History Log.

CH – Clear Alarm History

CH clears the Alarm History Log.

TD – Trend Data Table

TD displays the Trend Data Table, which monitors and

displays leakage current.

CT – Clear Trend Data Table

CT clears all records from the Trend Data Table.

TI – Display Date/time

TI displays the LD5100’s current date and time

MT ON – Measurement Trace

On

MT ON displays advanced manufacturer diagnostics of the

microprocessor.

MT OFF – Measurement

Trace Off

MT OFF turns off the display of advanced manufacturer

diagnostics of the microprocessor.

MBT – Modbus Trace On

MBT shows Modbus trace.

MBS – Modbus Stats

MBS shows Modbus stats.

EX – Exit

EX is used to enter the Bootloader command section. The

unit will stop monitoring cable and allow firmware updates

to be loaded. To restore normal operation after updating

firmware, type RUN and press the Enter (<-|) key on the

keyboard, or power the unit off and then back on again.