Leak Detection Modbus Master

B.3.

Configuring the LD5100 Via the EIA-232 (Craft)

Port

First, the Com Port Setting must be configured on the LD5100:

1

Using the Local display (LCD) on the LD5100 press any of the buttons. Move the cursor

down and select the Com Port Settings, press Enter to access the menu.

2

The cursor will be to the left of Port1, press the Enter key.

3

Push the DOWN arrow to change the type from Modbus-Slave to Modbus-Master, press

Enter to save the changes.

4

Connect the straight through male-female DB-9 serial cable from your laptop, or PC, to the

EIA-232 port on the LD5100.

5

Open the terminal emulation program (HyperTerminal) with a connection of 9600 Baud, 8

Data bits, Parity None, 1 Stop bit and Flow control set to off.

6

Press the Enter key on your laptop, or PC, to view the LD5100 Help menu.

7

Type “SC” to access the System Configuration menu (see Figure B.3).

Figure B.3 Configuration Menu from EIA-232 Connection