beautypg.com

20ma output testing, Figure 4.1, 20ma testing – RLE LD5100 User Manual

Page 29: Utput, Esting

background image

www.rletech.com

29

970.484.6510

C

H A P T E R

C

HAPTER

0

4-20

M

A O

UTPUT

T

ESTING

The LD5100’s 4-20mA output is loop powered and tested by the manufacturer. The

manufacturer guarantees its performance upon delivery. Should the 4-20mA output need to be

tested in the field, follow these steps. The following procedure is performed with the cable

connected, unless otherwise indicated.

1

Remove the two position plug from TB6.

2

Remove any wires from the terminal and

install a 200Ohm resistor to TB6-2. Then

apply +24V to TB6-1 and ground of the

24V supply to the other side of the

resistor.

3

Reinstall the plug on TB6.

4

With the system on and no alarms present,

measure the DC voltage across the

resistor. A value of 0.8VDC should

register. This equates to 4mA, or normal

operation.

5

Remove the SeaHawk Leak Detection

Cable (SC) and wait for the unit to activate

its cable trouble alarm. Measure the DC

voltage across the resistor. A value of approximately 4.0VDC should be measured. This

equates to 20mA, or a fault alarm. Reconnect the SC cable.

6

Place water on the end of the SC cable. Measure the DC voltage across the resistor. The

value will be proportional to the length of cable measured by the LD5100. A value of

approximately 4.0V, which equates to 20mA, will be read if the length of the cable is

identical to the length read by the LD5100. Dry the cable.

7

Place water on the start of the cable. Measure the DC voltage across the resistor. A

measurement of approximately 0.8VDC, or 4mA, should be measured. This corresponds to

a leak at zero distance. Dry the cable.

8

Remove the resistor from the plug and reattach any wires as necessary.

Figure 4.1 4-20mA Testing