LCD Interface
5.8.10 Language
The Language option designates whether the LD5100's LCD menus are displayed in English or
French.
5.8.11 Cable Test Relay
The Cable Test Relay option activates the internal test circuit to simulate 2500 feet (762m)
cable. This allows the SC cable to be removed from the LD5100 without causing alarms. The
Cable Test Relay will stay on for 300 seconds and a counter will be displayed.
5.8.12 Restore Defaults
The Restore Defaults option will reset all configurations back to the original factory defaults.
5.8.13 Clock
The Clock option allows users to set the time and date for the LD5100.
5.8.14 Resistance/Foot (Res/Ft)
The Res/Ft option allows users to precisely calibrate the LD5100. Users can adjust the ohms per
foot until the cable length displayed matches the actual cable length installed. The default value
is 2.800 ohms per foot.