Leak detection modbus master, B.1. connecting distance read panels to the ld5100, Connecting distance read panels to the ld5100 – RLE LD5100 User Manual

Page 61: Figure b.1 ld5100 connection diagram, Etection, Odbus, Aster

background image

www.rletech.com

61

970.484.6510

A

P P E N D I X

C

HAPTER

0

L

EAK

D

ETECTION

M

ODBUS

M

ASTER

This feature allows the LD5100 to act as a Modbus master, so it can talk to other RLE distance

read panels. Up to 11 RLE distance read panels can be connected to the EIA-485 port#1 on the

LD5100. The system status can be viewed by using the view zones menu. The LD5100 will

display leak, cable break, cable contamination, and loss of communications alarms from the

slave units connected to it.

B.1.

Connecting Distance Read Panels to the LD5100

When using the LD5100 as a Modbus master, the slave unit(s) must be wired to the EIA-485

port #1 (TB3). Port #2 (TB2) on the LD5100 can only be used as a Modbus slave output.

Using a two wire configuration, connect the slave units in a 485 daisy chain. You will have to

set the EIA-485 slave address in each Leak detection unit. The first unit connected must be set

to address 2. The following units will increase in numeric order by one unit (e.g., the next unit

would be set to address 3, the following would be set to address 4, etc.; see Figure B.1.)

Figure B.1 LD5100 Connection Diagram