This document describes the Modbus communications protocol as supported by the LD5100

Water Leak Detection System. It includes details and information on how to configure the

LD5100 for communications via Modbus network.

8.1. Implementation

Basics

The LD5100 is capable of communicating via the half-duplex RS485 serial communication

standard. The LD5100 is configured to act as a slave device on a common network. The

RS485 medium allows for multiple devices on a multi-drop network. The LD5100 is a slave

only device and will never initiate a communications sequence.

8.1.1 Modes of Transmission

The Modbus protocol uses ASCII and RTU modes of transmission. The LD5100 supports only

the RTU mode of transmission, with 8 data bits, no parity and one stop bit. Every Modbus

packet consists of four fields:



Slave Address Field



Function Field



Data Field



Error Check Field (Checksum)

8.1.1.1 Slave

Address

Field

The slave address field is set by the going into local 160x160 display on the front panel. Go to

COMM PORT SETTINGS from the Main Menu screen. Select the Modbus Slave address and

the baud rate to be used for either/or EIA-485 Port1 and EIA-485 Port2.