PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12
flowserve.com
Parameter
Transducer Block Description
SCALED_VALUES
(Index 96)
Manufacturer-specific parameter that contains an array of three 16-bit words:
Array Index 0:
Bit 0 – APT (Analog Position Transmitter)
APT Enabled = 1
APT Disabled = 0
Bit 1 – APT Polarity:
1 = high value 20 mA
0 = high value 4 mA
Bit 2 – ATT (Analog Torque Transmitter)
ATT Enabled =1
ATT Disabled = 0
Bit 3 – ATT Polarity:
1 = high value 20 mA
0 = high value 4 mA
Bit 4 – DDC Offset:
1 = 4 mA
0 = 0 mA
Bits 5-8 – Not Used
Bits 9-10 – Scaling:
0 = 0-100
1 = 0-255
2 = 0-4,095
Bits 11-15 – Not Used
Array Index 1: APT Modbus Register 3 (word)
Array Index 2: ATT Modbus Register 4 (word)
SELF_CALIB_CMD
(Index 49 – Not Used)
Initialization of a device-specific (manufacturer-specific) calibration procedure
SELF_CALIB_STATUS
(Index 50 – Not Used)
Result of status of the device-specific calibration procedure.
SETP_CUTOFF_DEC
(Index 54)
When the servo setpoint goes below the defined percent of span, the position
goes to the limit position CLOSE.
SETP_CUTOFF_INC
(Index 55)
When the servo setpoint goes above the defined percent of span, the position
goes to the limit position OPEN.
TARGET_ERROR
(Index 103 – Not Used)
Manufacturer-specific parameter.
TP_STATUS
(Index 100)
Manufacturer-specific parameter that contains an array in 16-bit word format:
Array Index 0: Unused
Array Index 1: Start_Position
Array Index 2: Stop_Position
Array Index 3: Num_Samples
Array Index 4: Max_Torque_Mid
Array Index 5: Max_Torque_Position
Array Index 6: Avg_Torque
Array Index 7: Stop_Torque
Array Index 8: Max_Torque_BOT
Array Index 9: Max_Torque_EOT