PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12

64

Channel 348

DI_POSITION_CHAN

Value

Opened

0x01

Closed

0x02

Opening

0x04

Closing

0x08

Stop

0x10

Channel 349 – Actuator Faults 1 (Index 109)

This channel, DI_ACTUATOR_FAULTS_1_CHAN, makes actuator faults available to DI function
blocks. The reported faults include:

• Valve jammed in motion due to a tripped torque switch.
• Valve was manually moved with the actuator handwheel.
• An over-torque condition while traveling.
• Loss of electrical phase.
• Thermal overload indicating the motor has overheated and the thermistor has opened.

Channel 349

DI_ACTUATOR_FAULTS_1_CHAN

Value

Monitor Relay

0x01

Valve Jammed

0x02

Manual Moved

0x04

Over Torque

0x08

Phase Error

0x10

Motor Over Temp

0x20

Monitor Relay + Valve Jammed

0x03

Monitor Relay + Manual Moved

0x05

Monitor Relay + Over Torque

0x09

Monitor Relay + Phase Error

0x11

Monitor Relay + Motor Over Temp

0x21

Monitor Relay + Valve Jammed + Manual Moved

0x07

Monitor Relay + Valve Jammed + Phase Error

0x13

Monitor Relay + Valve Jammed + Motor Over Temp

0x23

Channel 350 – Actuator Faults 2 (Index 110)

This channel, DI_ACTUATOR_FAULTS_2_CHAN, makes actuator faults available to other function
blocks. The reported faults include:

• Valve jammed in motion due to a tripped torque switch.
• Valve was manually moved with the actuator handwheel.
• An over-torque condition occurred while traveling in the open direction.
• An over-torque condition occurred while traveling in the close direction.
• Loss of electrical phase at the motor.
• Thermal overload indicating the motor has overheated and the thermistor has opened; time is

required for the motor to cool and reset the thermistor.