Flowserve MX/QX Profibus DP/PA Field Unit User Manual
Page 64

PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12
64
Channel 348
DI_POSITION_CHAN
Value
Opened
0x01
Closed
0x02
Opening
0x04
Closing
0x08
Stop
0x10
Channel 349 – Actuator Faults 1 (Index 109)
This channel, DI_ACTUATOR_FAULTS_1_CHAN, makes actuator faults available to DI function
blocks. The reported faults include:
• Valve jammed in motion due to a tripped torque switch.
• Valve was manually moved with the actuator handwheel.
• An over-torque condition while traveling.
• Loss of electrical phase.
• Thermal overload indicating the motor has overheated and the thermistor has opened.
Channel 349
DI_ACTUATOR_FAULTS_1_CHAN
Value
Monitor Relay
0x01
Valve Jammed
0x02
Manual Moved
0x04
Over Torque
0x08
Phase Error
0x10
Motor Over Temp
0x20
Monitor Relay + Valve Jammed
0x03
Monitor Relay + Manual Moved
0x05
Monitor Relay + Over Torque
0x09
Monitor Relay + Phase Error
0x11
Monitor Relay + Motor Over Temp
0x21
Monitor Relay + Valve Jammed + Manual Moved
0x07
Monitor Relay + Valve Jammed + Phase Error
0x13
Monitor Relay + Valve Jammed + Motor Over Temp
0x23
Channel 350 – Actuator Faults 2 (Index 110)
This channel, DI_ACTUATOR_FAULTS_2_CHAN, makes actuator faults available to other function
blocks. The reported faults include:
• Valve jammed in motion due to a tripped torque switch.
• Valve was manually moved with the actuator handwheel.
• An over-torque condition occurred while traveling in the open direction.
• An over-torque condition occurred while traveling in the close direction.
• Loss of electrical phase at the motor.
• Thermal overload indicating the motor has overheated and the thermistor has opened; time is
required for the motor to cool and reset the thermistor.