Channel 344 – Set Actuator Position (Index 104)
This channel, AO_CTRL_VALVE_FLOW_CHAN, is used to set the position of the actuator when it is
locally configured to run in the Position mode.
Control valve is in units of 0-100%.
AO_CTRL_VALVE_FLOW_CHAN will only function when the actuator is in Position mode. Position
mode is selected using the setup menus; refer to Bulletin LMENIM2306.
Channel 347 – Position and Bus Mode (Index 107)
This channel, DI_POSITION_AND_BUS_MODE_CHAN, makes actuator status information available to
other function blocks. The status information describes the position of the actuator (open or closed)
the direction of motion of the actuator (opening or closing), and the operating mode (Local, Remote,
or Stop [off]).
Channel 347
DI_POSITION_AND_BUS_MODE_CHAN
Value
Opened + Remote
0x21
Closed + Remote
0x22
Opening + Remote
0x24
Closing + Remote
0x28
Stop + Remote
0x30
Opened + Local
0x41
Closed + Local
0x42
Opening + Local
0x44
Closing + Local
0x48
Stop + Local
0x50
Opened + Stop
0x81
Closed + Stop
0x82
Opening + Stop
0x84
Closing + Stop
0x88
Stop + Stop
0x90
Channel 348 – Position Channel (Index 108)
This channel, DI_POSITION_CHAN, makes actuator status information available to other function
blocks. The status information describes the position or direction of motion of the actuator, that is,
either Opened, Closed, Opening, Closing, or Stop.