A appendix – wiring diagrams, Profibus dpv1 wiring diagram, Control panel – Flowserve MX/QX Profibus DP/PA Field Unit User Manual
Page 56

PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12
56
A Appendix – Wiring Diagrams
PROFIBUS DPV1 Wiring Diagram
CONTROL PANEL
SENSOR
POSITION
SENSOR
TORQUE
SENSOR
THERMAL
24V DC +Ve
0V DC
DIG COM #3-Ve
33
GR
OUP 3
CONTROL
SUPPLY
SEE
2
NOTE
DIG COM #3A
INPUT 0
32
30
DIG COM #2-Ve
31
DIG COM #2A
INPUT 1
29
34
INPUT 2
35
GR
OUP 2
OPEN
28
DIG COM #1-Ve
STOP
25
26
CLOSE
27
GR
OUP 1
21
22
0% OPEN
STATUS OK
OPEN
CLOSE
(YES)
(NO)
REMO
TE
LOCAL
(SEE NOTE 4)
MOTOR
"CLOSE"
POSITION
"OPEN"
POSITION
(SEE NOTES 3 & 5)
RELAYS
PRIMARY
50
51
47
46
48
49
45
44
S2
S1
a
b
a
b
- 5W MAX. EXT. LOAD
2. REMOTE INPUT JUMPERS
INPUT 0 - ESD,
INPUT 1 - OPEN INHIBIT,
INPUT 2 - CLOSE INHIBIT.
1. REMOTE INPUTS
DEFAULT INPUT CONFIGURATION:
POLARITIES ARE CORRECT.
JUMPERS CAN BE USER WIRED TO CONNECT DIG COMMONS
#1, 2 & 3 (AS NEEDED). THE 3 REMOTE WIRING GROUPS
ARE ELECTRICALLY ISOLATED, INTERNALLY. ONLY A SINGLE
POWER SOURCE MAY BE USED TO POWER ANY ONE GROUP
BUT DIFFERENT SOURCES MAY POWER DIFFERENT GROUPS.
IF DIFFERENT SOURCES ARE USED, ENSURE THAT THE
4. MAXIMUM EXTERNAL LOAD
REQUIRED CONTROL SIGNAL DURATION = 350ms MIN.
2 mA / 24V DC
MAX LOAD - 10 mA / 110V AC
MAXIMUM "OFF" 5.0V AC/DC
SIGNAL THRESHOLD - MINIMUM "ON" 19.2V AC/DC
INPUTS 0,1,2 ARE FIELD CONFIGURABLE FOR
CLOSE/OPEN INHIBIT, USER INPUT, OR ESD.
IN ADDITION, INPUT 2 MAY BE CONFIGURED
FOR CSE REMOTE SELECTION INDICATION.
TERMINALS 21 AND 22 (24 VDC)
3. DEFAULT [S] SETTINGS
THE DEFAULT OPERATING CONFIGURATION FOR THE
"S" OUTPUTS ARE SHOWN IN THE TABLE BELOW.
THE CONTACT STATES SHOWN IN THE SCHEMATIC
REPRESENT A FULLY CLOSED VALVE.
OUTPUT SWITCH CONTACT DEVELOPMENT
VALVE POSITION
FULL
CLOSE
FULL
OPEN
FUNCTION
CLOSE LIMIT
OPEN LIMIT
S1a
OUTPUT
SWITCH
OPEN CONTACT
CLOSED CONTACT
S2b
S2a
S1b
SEE OPERATION MANUAL FOR ALTERNATE CONFIGURATIONS.
5. CONTACT RATINGS
S1, S2- 0.5 AMP @ 125 VAC, 2 AMPS @ 30 VDC (RESISTIVE)
MONITOR- 0.5 AMP @ 125 VAC, 2 AMPS @ 30 VDC (RESISTIVE)
6. COMMAND PRIORITY
PLEASE SEE INSTALLATION AND OPERATION MANUAL
LMENIM 3306 FOR NETWORK COMMAND PRIORITIES.
PROFIBUS DPV1
PBDP-A (+) OUT
PBDP-A (-) OUT
SURGE
3
14
13
4
5
PBDP-A (+) IN
PBDP-A (-) IN
PER IEC 61158-2
POWER SUPPLY