PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12

32

7. The unit will display PB ADDRESS 1–OK? If OK, select YES. If NO, select different address

(1-125).

8. Select YES to proceed to the ANALOG SCALE display.

9. From ANALOG SCALE, if the default value of 0-100 is OK, select YES. If not, select NO.

10. If YES is selected, ESD ACTION (IGNORE) – OK? is displayed.

11. For ignoring ESD ACTION, select YES. For setting ESD ACTION, select NO. If POSITION is chosen

as action, ESD MOVE TO (XXX%)-OK? is displayed. Select NO to set desired position.

12. If YES is selected, COMM LOSS ACTION (NONE) – OK? is displayed.

13. For no COMM LOSS ACTION, select YES. For setting COMM LOSS ACTION, select NO. If

POSITION is chosen, as action, MOVE TO XXX% OPEN is displayed. Select NO to set desired
position.

14. If YES is selected, COMM LOSS DELAY (60 SEC) – OK? is displayed.

15. For a 60-second delay, select YES. Otherwise, select NO until the required value is displayed.

16. If YES is selected, OPEN/CLOSE MODE-OK? is displayed.

17. For OPEN/CLOSE MODE, select YES. For POSITION MODE, select NO. In position mode, the host

device can set the valve position to any desired value; in OPEN/CLOSE MODE the host can only
fully open or fully close the valve. The user must locally configure one of these two modes.

18. Proceed to configure the proportional band and deadband as discussed in sections 2.5.1 and

2.5.2, respectively.

Figure 2.22 – MX/QX PB PA Setup Sequence

Figure 2.22 illustrates the setup sequence for the MX/QX PB PA. For proper operation, either Position
Mode or Open/Close Mode must be selected.

Follow these steps to enter and configure the setup mode:

NO

(OFF)

YES

NO

NO

NO

YES

YES

YES

YES

(1%-100%)

1% Increments

(1%-50%)

1% Increments

CHANGE

PB/PA?

STATUS

(ON)-OK?

YES

CHANGE PROP/

DEADBAND?

NO

YES

DEADBAND

(2%)-OK?

PROP BAND

(15%)-OK?

NO

OPEN/CLOSE

MODE-OK?

POSITION

MODE-OK?

NO

YES

NO

YES

PB ADDRESS

(1)-OK?

(1-125)

Unit Increments

(CLOSE)

(OPEN)

(STOP)

(POSITION)

YES

NO

ESD ACTION

(IGNORE)-OK?

(CLOSE)

(OPEN)

(STOP)

(POSITION)

YES

YES

NO

COMM LOSS ACTION

(NONE)-OK?

(0-4095)

NO

COMM LOSS DELAY

(60 SEC)-OK?

(0-100%)

*

*

YES

NO

MOVE TO

XXX% OPEN

(0-100%)

YES

NO

MOVE TO

XXX% OPEN

ANALOG SCALE

0-100-OK?

* If P OS ITION is chosen, as action,

this menu will appear.