Figure 3.9 – discrete input function block – Flowserve MX/QX Profibus DP/PA Field Unit User Manual

Page 49

background image

49

PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12

flowserve.com

The FSAFE_VALUE_D (acyclic) parameter is the default value for the OUT_D parameter if a sensor
electronic fault is detected (e.g., the Transducer Block is unable to communicate with the actuator
hardware).

Supported Modes
Out of Service (O/S), Manual (Man), and Automatic (Auto) modes are supported. If Manual is
allowed, the operator may write a value to OUT_D using a configuration tool.

Simulate (acyclic)
For commissioning and test purposes, the input value from the transducer block going to the
Discrete Input function block can be simulated. That means the transducer and DI-FB will be discon-
nected when simulation is enabled. The network user can provide the DI block with “fake” process
data to test other portions of the system.

This feature requires the installation of a hardware jumper on the MX/QX PB unit, located on header
X5, Pins 3-4.

Figure 3.8 – Summary of the Parameters of the Discrete Input Function Blocks

DI

Function

Block

OUT_D

Standard Configuration Parameters

(Acyclic Data)

Example: CHANNEL

INVERT

SIMULATE

Process Parameter

(Cyclic Data)

Figure 3.9 – Discrete Input Function Block

Discrete Input Function Block

Enable

Simulate

Valve and

Status

FB Algorithm

Operator

Value Status

Value

Off

On

Value Status

Fail Safe

MODE- and STATUS-

Handling

OUT

OUT

Operator

AUTO

Status

MAN

Out of

Service

OUT_D

Simulate Parameter

Acyclic Configuration Parameters

PV_D from Transducer

Block Selected Channel

Typical for Discrete Position,

Faults, or Alarms

Data from

Actuator Hardware

Cyclic Process

Parameter

To Network User

Status