PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12

flowserve.com

Figure 3.7 – Analog Output Block Scaling

Temp = (SP – EU 0%) / (EU 100% – EU 0%)

PV_SCALE

PV_SCALE PV_SCALE

READBACK

PV = Field_Val * (EU 100% - EU 0%) + EU 0%

OUT_SCALE

OUT

PV_SCALE

OUT_SCALE

Transducer Block Value

FB-Algorithms

SP / RCAS_IN

OUT = Temp (EU 100% – EU 0%) + EU 0%

OUT_SCALE OUT_SCALE OUT_SCALE

Temp = (PV – EU 0%) / (EU 100% – EU 0%)

OUT_SCALE

OUT_SCALE OUT_SCALE

READBACK = Temp (EU 100% – EU 0%) + EU 0%

PV_SCALE PV_SCALE PV_SCALE

FSAVE_TYPE (acyclic) defines the reaction of the device if failure of actual used setpoint is still
detected after FSAVE_TIME or if the status of actual used setpoint is Initiate Fail Safe. The calculated
ACTUAL MODE is AUTO respectively.

FSAVE_TYPE

0

Value FSAVE_VALUE is used as setpoint, status of OUT = UNCERTAIN – Substitute Value.

1

Storing last valid setpoint, status of OUT = UNCERTAIN – Last usable Value or BAD – No commu-

nication, no LUV.

2

Actuator goes to fail-safe position defined by ACTUATOR_ACTION (only useful for actuators with

spring return), status of OUT = BAD – non-specific.

FSAVE_VALUE (acyclic) is the setpoint used if FSAVE_TYPE = 0 and FSAVE is activated.