B appendix – feature definitions, Transducer block i/o channels – Flowserve MX/QX Profibus DP/PA Field Unit User Manual
Page 62

PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12
62
B Appendix – Feature Definitions
Transducer Block I/O Channels
The following section defines the Transducer Block I/O channels available for use by the function blocks.
The transducer block for the MX/QX PB is located in Slot 9 of the device. Standard parameters start
at Index 16 of the slot. Manufacturer-specific parameters begin with an offset index of 80; therefore,
these parameters begin at index 96.
Transducer blocks are referenced by channel numbers. The references are parameters of the function
block and are used to logically associate transducer and function block information. During block
configuration, the value of the transducer block channel number may be configured for input and
output function blocks.
All I/O channels contain one byte for Status.
Channel
Channel Name
Description
344
AO_CTRL_VALVE_FLOW_CHAN
Desired valve position %
347
DI_POSITION_AND_BUS_MODE_CHAN
Valve status and control mode
348
DI_POSITION_CHAN
Valve status, moving/stopped
349
DI_ACTUATOR_FAULTS_1_CHAN
Mechanical and electrical faults 1
350
DI_ACTUATOR_FAULTS_2_CHAN
Mechanical and electrical faults 2
351
DI_ACTUATOR_ALARMS_CHAN
Emergency shutdown and inhibits
352
DI_DISC_USER_INPUT_CHAN
Discrete input from user
353
DI_READ_DISC_OUTPUT_CHAN
Read discrete output
354
DO_POSITION_CHAN
Command Stop/Open/Close
355
DO_ESD_CHAN
Command Emergency Shutdown
356
DO_RELAY_CHAN
Command Energize Relays
357
AI_POSITION_CHAN
Current valve position (0-100%)
358
AI_ANALOG_INPUT_1_CHAN
Value of analog input 1 (0-100%)
359
AI_ANALOG_INPUT_2_CHAN
Value of analog input 2 (0-100%)
The actuator PROFIBUS control contains four discrete input (DI) bocks. However, as described below,
there are seven DI channels to choose from, so three channels are inactive.
Details of the channels are shown in the following tables.