beautypg.com

Monitor) stored events, Monitor) comm-state (communications), A.5.3 (monitor) stored events – Comtech EF Data CRS-400 User Manual

Page 70: A.5.4 (monitor) comm-state (communications), A.5.3.1 (monitor, stored-events) view, A.5.4 (monitor) comm-state (c

background image

CRS-400 1:8 Redundancy Switch

Revision 0

Remote Control

MN/CRS400.IOM

54

A.5.3 (MONITOR) STORED EVENTS

STORED EVENTS: VIEW
CLEAR-ALL (PRESS ENTER)


Select VIEW or CLEAR ALL, using the LEFT/RIGHT arrow keys, then press ENTER.
CLEAR ALL does not prompt for confirmation–the command acts immediately.

A.5.3.1 (MONITOR, STORED-EVENTS) VIEW

LOG23: 26/01/00 10:37:32
FT-06 DMD ALARM (UP/DN)


Use the UP/DOWN arrow keys to scroll backwards or forwards through the entries in the
event log. To return to the previous menu, press ENTER or CLEAR.

The event log can store up to 98 events. When a fault condition occurs, it is time-stamped
and put into the log. Next to the FT (for fault) indicator is either the TM number, RM
(redundant mod/demod fault) or SW (switch fault). Similarly, when the fault condition
clears, this is also recorded, as shown below:

LOG23: 26/01/00 10:37:35
OK-06 DMD ALARM (UP/DN)


To clear the Event Log, select CLEAR-ALL. The previous menu returns.

However, if there are faults present on the unit at this time, they will be re-time-stamped,
and new log entries will be generated.

Note: In accordance with international convention, the date is shown in DAY-MONTH-YEAR

format.

A.5.4 (MONITOR) COMM-STATE (C

OMMUNICATIONS

)

COMMS OK: MOD:1234-!--R
DMD:--345678R


This screen indicates which mods/demods have good EIA-485 I/O communications with
the switch.

An exclamation mark (!), if present, indicates the position of an I/O communications
problem. This is a position that has been activated, but a unit is not responding:

Check the bus address and communications settings

Check that the bus cable is properly attached.