Auto-Zone Plus

Section 4

Start-Up and Troubleshooting

4-5

CommLink IV

Multiple Loop

Network Loop

Terminal Block

Network Loop

Terminal Block

Local Loop

Terminal Block

Local Loop #1

Local Loop #2

Local Loop

Terminal Block

Network Loop

To Other Zone Managers

RS-485 Network

Communication

Loop

Address Set To 1

Address Set To 2

Computer

(Optional)

HVAC Unit #1

Zone

Manager

To HVAC Unit #1

Zone Controllers

And Constant Volume

Units If Used

To HVAC Unit #2

Zone Controllers

And Constant Volume

Units If Used

The Address Is Used To Describe

Which Loop We Are Referring To

HVAC Unit #2

Zone

Manager

Caution: Connect Only

Zone Managers & CommLink

To This Loop

Figure 4-1:

Communications Loop Overview


Each Zone Manager (HVAC unit) has a separate Local communications loop for
associated Zone Controllers and any Constant Volume units used.

Each Local loop must have a unique cluster address. It is typical for each Local loop to
have a sequential cluster address (e.g. 1, 2, 3, etc.).

Note:

No controllers should be connected to the Network communications loop.


The Network communications loop should only be connected to the MiniLink’s Network
terminals on the Zone Manager(s), and the CommLink IV.