Zone controller setpoints, Minimum default maximum – Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual
Page 119

Auto-Zone Plus
Section 3
Programming
3-33
Zone Controller Setpoints
Note: The top line always displays the currently selected Zone Controller and the
controller type.
PD ZONE ADDRESS
means a Pressure Dependent Zone is selected.
PI ZONE ADDRESS
means a Pressure Independent Zone is selected.
Setpoint Screen #1
Setpoint Screen #2
PD ZONE ADDRESS 1
OCCUPIED SETPOINTS
Cooling Setpt: 75°F
Heating Setpt: 72°F
The Occupied Heating and Cooling Setpoints are entered on
this screen. The Heating Setpoint should always be two
degrees below the Cooling Setpoint, or the Zone Controller
will not accept the new values. The System Manager can't
prevent the entry of invalid setpoints. If invalid setpoints are
entered, the previous settings will be retained by the system and
displayed the next time the Zone Setpoints are accessed.
Minimum Default Maximum
Cooling Setpoint
50°F
75°F
90°F
Heating Setpoint
50°F
72°F
90°F
PD ZONE ADDRESS 1
UNOCCUPIED SETPOINTS
Cool Setup...: 10°F
Heat Setback.: -10°F
The Unoccupied Heating and Cooling Setback values are
entered on this screen. The Occupied Cooling Setpoint will be
increased by the Cooling Setback during Unoccupied Mode
and the Heating Setpoint will be decreased by the Heating
Setback.
Minimum Default Maximum
Cool Setup
0°F
10°F
30°F
Heat Setback
0°F
-10°F
-30°F