Minimum default maximum, Setpoint screen #5, Setpoint screen #6 – Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual
Page 109: Setpoint screen #7

Auto-Zone Plus
Section 3
Programming
3-23
Setpoint Screen #5
Setpoint Screen #6
Setpoint Screen #7
SUPPLY AIR SETPOINTS
Cool SAT DB: 2°
Heat SAT DB: 2°
CoolStage Up: 3 Min
CoolStage Dn: 1 Min
Min Cool Run: 5 Min
Min Cool Off: 3 Min
HeatStage Up: 3 Min
HeatStage Dn: 1 Min
Min Heat Run: 5 Min
Min Heat Off: 3 Min
If you have configured your unit for DX cooling this screen
will appear. This is the deadband used for DX Cooling and
Heat Stages only, and is not used for modulating heating and
cooling. The deadband is the temperature differential above
or below the setpoint that will be used between stages of
cooling and heating when staging up or down.
Minimum Default Maximum
Cooling SAT DB
1
°F 2°F 10°F
Heating SAT DB
1
°F 2°F 10°F
If you have configured your unit for DX cooling this screen
will appear. This screen allows you to set the time delay used
between DX Cooling stages and also the minimum run time
and minimum off time for the compressors.
Minimum Default Maximum
CoolStage Up
1 Min
3 Min
15 Min
CoolStage Dn
1 Min
1 Min
15 Min
Min Cool Run
1 Min
5 Min
15 Min
Min Cool Off
1 Min
3 Min
15 Min
If you have configured your unit for Staged Heating this
screen will appear. This screen allows you to set the time
delay used between Heating stages and also the minimum
run time and minimum off time for the heating device.
Minimum Default Maximum
HeatStage Up
1 Min
3 Min
15 Min
HeatStage Dn
1 Min
1 Min
15 Min
Min Heat Run
1 Min
5 Min
15 Min
Min Heat Off
1 Min
3 Min
15 Min