Minimum default maximum, Setpoint screen #3, Setpoint screen #4 – Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual
Page 120

Section 3
Auto-Zone Plus
3-34
Programming
Setpoint Screen #3
Note: If slide effect is set to 0
°, the pushbutton override will not function.
Setpoint Screen #4
PD ZONE ADDRESS 1
AuxHeat Setpt: 72°F
Slide Effect.: 3°F
If your Zone Controller has the optional Relay Expansion
Board attached, one of the relays is reserved for an Auxiliary
Heating Relay. Enter that setpoint on the AuxHeat Setpt line. If
the relay board is not installed, this line will not be displayed.
If your Zone Temperature sensor has the optional Setpoint
Adjustment Slide, enter the maximum effect it can have on the
setpoints on the Slide Effect line.
Minimum Default Maximum
AuxHeat Setpt
50°F 72°F 90°F
Slide Effect
0°F
3°F
5°F
PD ZONE ADDRESS 1
Max Damper....: 100%
Cool Mode Min.: 5%
Heat Mode Min.: 20%
On Pressure Dependent Zones, these setpoints are for damper
position, on Pressure Independent Zones they are for Airflow
(CFM) values, and the text will change to reflect that.
Minimum Default Maximum
PD Zone Max Damper
PI Zone Max Airflow
0 %
0 CFM
100 %
800 CFM
100 %
30000 CFM
PD Zone Cool Mode Min
PI Zone Cool Mode
0 %
0 CFM
5 %
200 CFM
100 %
30000 CFM
PD Zone Heat Mode Min
PI Zone Heat Mode
0 %
0 CFM
20 %
300 CFM
100 %
30000 CFM