Configuration screen #12, Configuration screen #13, Configuration screen #14 – Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual
Page 105: Configuration screen #15

Auto-Zone Plus
Section 3
Programming
3-19
Configuration Screen #12
Configuration Screen #13
Configuration Screen #14
Configuration Screen #15
ZONE MAVERICK TEST
Testing is Enabled
Use Left/Right Arrow
Maverick zones are reported to the Zone Manager, if you have
some problem zones or during startup if not all of the sensors
are wired in, you may want to eliminate the Maverick testing.
To do this select Disabled instead of Enabled. To toggle
between the two modes, use the Left/Right Arrow keys.
The Zone Manager normally uses its own real-time clock and
an internal week schedule to determine the
Occupied/Unoccupied mode of operation. To use its own
internal schedule enter “0”. The Zone Manager does have the
ability to use a global broadcast from another scheduling
device on the communications loop if a more powerful
schedule is required. If an external schedule is used, the range
of schedule numbers is 1 to 7 and should be set to match the
external scheduling device schedule number desired.
Zone Manager
Uses Schedule #: 0
0 = Internal Clock
1-7 = External Clock
ECONOMIZER CONTROL
[0-10 VDC Range]
Use Left/Right Arrow
The Zone Manager has four voltage ranges to choose from for
control of the economizer damper. To toggle between 2-10
VDC, 10-0 VDC and 10-2 VDC, use the Left/Right Arrow
keys.
CW VALVE CONTROL
[0-10 VDC Range]
Use Left/Right Arrow
If you have a CW Valve for cooling and you selected that
option on Configuration Screen #8, this screen will appear. The
Zone Manager has four voltage ranges to choose from for
control of the chilled water valve. To toggle between 2-10
VDC, 0-10 VDC, 10-2 VDC and 10-0 VDC, use the Left/Right
Arrow keys.