Zone manager configuration, Minimum default maximum – Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual
Page 102

Section 3
Auto-Zone Plus
3-16
Programming
Zone Manager
Configuration
These configuration setpoints are normally entered only one time and then never accessed
again. This is why they occupy their own menu location, so the user is not required to step
through these during normal setpoint Read and Reset.
Note: On initial power up, the system must be configured before it can be
successfully operated.
Configuration Screen #1
Caution: The zones should be consecutively addressed with no skipped address
locations. If you do skip an address, the Zone Manager will presume
there is a missing zone, and an alarm will occur.
ZONE POLLING RANGE
First Zone Addr: 1
Last Zone Addr: 1
[0 = RA Control]
The Zone Manager needs to know the address range of the
attached Zone Controllers to be polled. The user enters the
addresses of the first and last zones here. If you are controlling
from Return Air Temperature instead of voting zones, input –1
for both the first and last address.
Minimum Default Maximum
First Zone
Addr
1 1 16
Last Zone Addr
1
1
16