Auto-Zone Plus
Section 3
Programming
3-21
Zone Manager Setpoints
Control Setpoints
Setpoint Screen #1
Setpoint Screen #2
Cooling Lockout
If the outside air temperature drops 1
° below this setpoint the
mechanical cooling is disabled. Cooling is re-enabled at 1
°
above this setpoint.
Heat Lockout
If the outside air temperature rises 1
° above this setpoint the
first stage of heat is disabled. The first stage of heat is re-
enabled at 1
° below this setpoint.
DUCT STATIC SETPOINT
Static Press: 0.5"
This screen will be displayed to allow you to enter the
controlling duct Static Pressure Setpoint.
Minimum Default Maximum
Static Press
0.1"
0.5"
2.0"
LOCKOUT SETPOINTS
Cool Lockout: 0°
Heat Lockout: 65°
The Mechanical Cooling and Heating Lockouts are entered on
this screen.
Minimum Default Maximum
Cool Lockout
-40°F
50°F
80°F
Heat Lockout
30°F
75°F
99°F