Technical features – CIRCUTOR CVM-C10 Series User Manual
Page 76
5�- TECHNICAL FEATURES
AC Power supply
Rated voltage
85 ... 265 V
~
Frequency
50 ... 60 Hz
Consumption
4 ... 6 VA
Installation category
CAT III 300 V
DC Power supply
Rated voltage
95 ... 300 V
20 ... 120 V
(1)
Consumption
2 ... 6 W
3.5 ... 3 W
Installation category
CAT III 300 V
(1)
Only available for references
M559110050000, M559210050000, M559210050V00 and M5594200500000.
Voltage measurement circuit
Rated voltage (Un)
300 V
Ph-N
, 520 V
Ph-Ph
Voltage measurement margin
5 ... 120% Un
Frequency measurement margin
45 ... 65Hz
Input impedance
440 kΩ
Min� voltage measurement (Vstart)
10 V
Installation category
CAT III 300 V
Current measurement circuit
Model
CVM-C10-ITF
CVM-C10-ITF-IN
CVM-C10-MC
CVM-C10-mV
Nominal current (In)
.../5A or .../1A
... / 0.250 A
.../0.333 A
Neutral current measurement
CVM-C10-IN-ITF
.../5A or .../1A
-
-
Current measurement margin
2 ... 120% In
2 ... 120% In
2 ... 120% In
Maximum current, impulse < 1s
100 A
100 A
1.2 In
Min� current measurement (Istart)
10 mA
MC1
MC3
6.66 mA
0.25 A
0.1 A
Installation category
CAT III 300 V
CAT III 300 V
CAT III 300 V
Measurement accuracy
Model
CVM-C10-ITF
CVM-C10-ITF-IN
CVM-C10-MC
CVM-C10-mV
Voltage measurement
0.5% ± 1 digit
0.5% ± 1 digit
0.5% ± 1 digit
Current measurement
0.5% ± 1 digit
0.5% ± 1 digit
0.5% ± 1 digit
Frequency measurement
0.5%
0.5%
0.5%
Active power measurement
0.5% ± 2 digits
1% ± 2 digits
0.5% ± 2 digits
Reactive power measurement
1% ± 2 digits
2% ± 2 digits
2% ± 2 digits
Active energy measurement
I < 0�1In
I > 0�1In
Class 1
Class 1
Class 1
Class 0.5
Reactive energy measurement
Class 2
Class 2
Class 2
Pulse outputs (CVM-C10-ITF CVM-C10-MC and CVM-C10-mV)
Quantity
2
Type
NPN ouputs
Maximum voltage
24 V
Maximum current
50 mA
76
CVM-C10
Instruction Manual