beautypg.com

Technical features – CIRCUTOR CVM-C10 Series User Manual

Page 76

background image

5�- TECHNICAL FEATURES

AC Power supply

Rated voltage

85 ... 265 V

~

Frequency

50 ... 60 Hz

Consumption

4 ... 6 VA

Installation category

CAT III 300 V

DC Power supply

Rated voltage

95 ... 300 V

20 ... 120 V

(1)

Consumption

2 ... 6 W

3.5 ... 3 W

Installation category

CAT III 300 V

(1)

Only available for references

M559110050000, M559210050000, M559210050V00 and M5594200500000.

Voltage measurement circuit

Rated voltage (Un)

300 V

Ph-N

, 520 V

Ph-Ph

Voltage measurement margin

5 ... 120% Un

Frequency measurement margin

45 ... 65Hz

Input impedance

440 kΩ

Min� voltage measurement (Vstart)

10 V

Installation category

CAT III 300 V

Current measurement circuit

Model

CVM-C10-ITF

CVM-C10-ITF-IN

CVM-C10-MC

CVM-C10-mV

Nominal current (In)

.../5A or .../1A

... / 0.250 A

.../0.333 A

Neutral current measurement

CVM-C10-IN-ITF

.../5A or .../1A

-

-

Current measurement margin

2 ... 120% In

2 ... 120% In

2 ... 120% In

Maximum current, impulse < 1s

100 A

100 A

1.2 In

Min� current measurement (Istart)

10 mA

MC1

MC3

6.66 mA

0.25 A

0.1 A

Installation category

CAT III 300 V

CAT III 300 V

CAT III 300 V

Measurement accuracy

Model

CVM-C10-ITF

CVM-C10-ITF-IN

CVM-C10-MC

CVM-C10-mV

Voltage measurement

0.5% ± 1 digit

0.5% ± 1 digit

0.5% ± 1 digit

Current measurement

0.5% ± 1 digit

0.5% ± 1 digit

0.5% ± 1 digit

Frequency measurement

0.5%

0.5%

0.5%

Active power measurement

0.5% ± 2 digits

1% ± 2 digits

0.5% ± 2 digits

Reactive power measurement

1% ± 2 digits

2% ± 2 digits

2% ± 2 digits

Active energy measurement

I < 0�1In

I > 0�1In

Class 1

Class 1

Class 1

Class 0.5

Reactive energy measurement

Class 2

Class 2

Class 2

Pulse outputs (CVM-C10-ITF CVM-C10-MC and CVM-C10-mV)

Quantity

2

Type

NPN ouputs

Maximum voltage

24 V

Maximum current

50 mA

76

CVM-C10

Instruction Manual