Maximum programming value: 999.999 KWh

Minimum programming value: 000.001 KWh

Example: To program 500 Wh per pulse: 000.500

To program 1.5 kWh per pulse: 001.500

Programming the pulse width

The width of the pulse is selected on this screen in ms.
Press key

for 3 seconds to edit the pulse width selection. The

prog icon will be displayed on the bottom of the screen.

To enter or modify the value, press the

key repeatedly,

increasing the value of the flashing digit.

When the desired value is shown on the screen, move onto the next digit by pressing the key

to modify the other values.

If you press the

key after changing the last digit, it will jump back to the first digit so you

can modify the previously programmed values again.

To validate the data, press

for 3 seconds and the

prog icon will disappear from the display.

Press key

to access the next programming step.

The programmed value will be deleted if the entered value is higher than the maximum

programming value.

Maximum programming value: 500 ms.

Minimum programming value:

30 ms.

4�9�25� Programming alarm 4 (Digital output T2)

All values for digital output T2 are programmed on this screen.

They are programmed as in the case of digital output T1, see

“4.9.24. Programming alarm 3 (Digital output T1)”

55

Instruction Manual

CVM-C10