4�9�6�Secundary neutral current (model CVM-C10-ITF-IN)
The neutral current transformer secundary is programmed on this
screen.
Press key
for 3 seconds to edit the transformer secundary
value. The
prog icon will be displayed on the bottom of the
screen.
Press key
to browse the two possible options for the current
transformer secondary (1A or 5A).
To validate the data, press
for 3 seconds and the
prog icon will disappear from the display.
Press key
to access the next programming step
4�9�7� Number of quadrants
The quadrant number on which the unit takes the measurement
is selected on this screen.
Press key
for 3 seconds to edit the number of quadrants. The
prog icon will be displayed on the bottom of the screen.
Press key
to browse the two options:
2 or 4 quadrants.
To validate the data, press
for 3 seconds and the
prog icon will disappear from the display.
Press key
to access the next programming step
4�9�8� Type of installation
The type of installation is selected on this screen.
Press key
for 3 seconds to edit the type of installation. The
prog icon will be displayed on the bottom of the screen.
The
key is used to browse the different options
Three-phase network measurement with a 4-wire connection.
Three-phase network measurement with a 3-wire connection.
Three-phase network measurement with a 3-wire connection and
transformers with an ARON connection .
Two-phase network measurement with a 3-wire connection.
Single-phase network measurement, phase to phase, with a 2-wire connection.
40