In the case of some parameters (

Table 14

) you can modify the position of the decimal point.

To do so, press key

after modifying the last digit and the decimal point will start flashing.

Press key

repeatedly to modify the position of the decimal point.

To validate the data, press

for 3 seconds and the

prog icon will disappear from the display.

Press key

to access the next programming step.

Programming the connection time delay

The alarm connection delay is programmed on this screen in

seconds.
Press key

for 3 seconds to edit the delay selection. The

prog

icon will be displayed on the bottom of the screen.
To enter or modify the value, press the

key repeatedly,

increasing the value of the flashing digit.

When the desired value is shown on the screen, move onto the next digit by pressing the key

to modify the other values.

If you press the

key after changing the last digit, it will jump back to the first digit so you

can modify the previously programmed values again.

To validate the data, press

for 3 seconds and the

prog icon will disappear from the display.

Press key

to access the next programming step.

Programming the hysteresis value

The hysteresis value, i.e., difference between the alarm

connection and disconnection value, in %, is programmed on

this screen.
Press key

for 3 seconds to edit the hysteresis value

selection. The

prog icon will be displayed on the bottom of the

screen.
To enter or modify the value, press the

key repeatedly,

increasing the value of the flashing digit.

When the desired value is shown on the screen, move onto the next digit by pressing the key

to modify the other values.

If you press the

key after changing the last digit, it will jump back to the first digit so you

can modify the previously programmed values again.

To validate the data, press

for 3 seconds and the

prog icon will disappear from the display.

Press key

to access the next programming step.

51

Instruction Manual

CVM-C10